CABLE MKShng 2х0,5
TU U 27.3-33527835-016:2019
Installation cable with tinned copper conductors, with insulation and sheath made of polyvinyl chloride plastic.
The abbreviation MKShng is decoded as follows:
CONSTRUCTION
TECHNICAL SPECIFICATIONS
Operating temperature of the surrounding environment from -50°C to +50°C.
Relative humidity at a temperature of +35°C – 98%.
Permissible long-term temperature for heating current-carrying conductors during operation +70°C.
Installation of cables without preheating can be performed at ambient temperatures no lower than -15°C.
Electrical resistance of cable insulation, calculated per 1 km length and at a temperature of 20 °C, is not less than 10 MΩ.
Test alternating voltage with a frequency of 50 Hz is 2000 V for 5 minutes.
Minimum bending radius during installation – 5 times the cable diameter.
Construction length of the cable is no less than 25 meters.
Warranty period of operation – 3 years from the date of commissioning.
APPLICATION
Cables are designed for fixed inter-device installation of electrical devices operating at a rated alternating voltage of up to 500 V with a frequency of up to 400 Hz or a direct voltage of up to 750 V.
Why buy MKShng 2х0,5 cable from "Energoalliance"
It is more profitable to purchase cable products wholesale or retail directly from the manufacturer. "Energoalliance" is one of the industry leaders. The company has been known on the market since 2005 and offers certified products at affordable prices. The assortment includes power, installation, and control cables. We cooperate with electrical installation companies, utilities, factories, and private individuals. The company works with customers from Ukraine, CIS, and Europe, offering comfortable individual terms of cooperation. The delivery price depends on the current postal service rates.