CABLE PAL
TU U 27.3-33527835-014:2019
Wire with heat-resistant insulation
The abbreviation PAL stands for:
CONSTRUCTION
TECHNICAL SPECIFICATIONS
The operating temperature of the ambient environment ranges from -50 °C to +200 °C.
Wire installation without preheating can be performed at an ambient temperature not lower than -15 °C.
The electrical resistance of the wire insulation, brought to a temperature of 20 °C, is at least 1·1010 Ω·m.
Test alternating voltage frequency 50 Hz – 4000 V, 1 minute.
Minimum bending radius during installation – 15 wire diameters.
Wire construction length is at least 10 meters.
Warranty period of operation – 1.5 years from the date of commissioning.
APPLICATION
The wires are designed for stationary installation in electrical installations, in lighting networks, for the installation of electrical equipment, machines, mechanisms, and devices at a nominal voltage of up to 660 V AC frequency of 50 Hz.
Estimated diameter and weight of 1 km of wire
Nominal conductor cross-section, mm² |
Maximum outer diameter of the wire, mm |
Estimated weight of the wire, kg/km |
---|---|---|
0.75 | 4.4 | 27.8 |
1 | 4.5 | 30.6 |
1.5 | 5.2 | 38 |
2.5 | 5.8 | 55.5 |
4 | 6.4 | 72.2 |
6 | 7.4 | 103 |
10 | 8.5 | 147 |
16 | 9.9 | 221 |
25 | 11.1 | 316 |
35 | 13.8 | 456 |
50 | 15 | 592.2 |
Why choose PAL cable from Energoalliance
Buying cable products in bulk directly from the manufacturer is more cost-effective. Energoalliance is one of the industry leaders. The company has been known on the market since 2005 and offers certified products at affordable prices. The assortment includes power, installation, and control cables. We cooperate with electrical installation companies, municipal enterprises, factories, and private individuals. The company works with clients from Ukraine, the CIS, and Europe, offering comfortable individual cooperation terms. Delivery cost depends on the current postal service tariffs.